ETCR8600B contains 15 gear current values, but how does ETCR8600B set the current gear?
Function rotary switch
1. V~ gear: This symbol is the AC voltage test gear, this gear can measure AC voltage below 600V;
2. ×1/2 gear : This gear indicates that the current displayed in the setting window is ×1/2, which is also half of the current displayed in the window;
3. ×1 gear : This gear represents the ×1 of the current displayed in the setting window, which is the same as the current displayed in the window;
4. ×2 gear : This gear represents the ×2 of the current displayed in the setting window, which is twice the current displayed in the window;
5. Auto : This gear indicates automatic mode. In automatic mode, the meter automatically outputs from low current to high current in sequence until an action occurs.
Current Setting
Set default value : 10mA / 20mA / 30mA / 100mA / 300mA / 500mA
Corresponding Gear Value
Current setting
10mA
20mA
30mA
100mA
300mA
500mA
X1/2 gear mode
5mA
10mA
15mA
50mA
150mA
250mA
X1 gear mode
10mA
20mA
30mA
100mA
300mA
500mA
X2 gear mode
20mA
40mA
60mA
200mA
600mA
1000mA
ETCR8600 Leakage Protector Tester is designed to test the line AC voltage, leakage initiating current, residual non-operating current and leakage initiating separation time of various leakage protectors online, the test current from 5~1000mA with 16 grade (5、10、15、20、30、40、50、60、100、150、200、250、300、500、600、1000mA), range of the leakage initiating separation time is 0~999ms.The required output current value can be set according to the table