Overview
ETCR9150B Wireless H/L Voltage Clamp Meter break through the traditional structure, specially designed and manufactured for measuring high voltage current, the tester adopts CT technology and mask digital integration technology, the instrument composed of special clamp current meter and high voltage insulation rod, equipped with wireless receivers, which can receive the tested data within 30M straight-line distance. If not use insulation rod, which can be used as high accuracy low voltage clamp current meter.
ETCR9150B Wireless H/L Voltage Clamp Meter, the innovative integrated design of the clamp and the guide area ensures the high accuracy, high reliability and high stability of year-round uninterrupted testing.
ETCR9150B Wireless H/L Voltage Clamp Meter connect with insulation rod, which can use for high voltage line current measurement of the wire with insulation skin below 110KV online current measurements, also with peak hold, data hold and data storage and so on others functions, the special clamp current meter convenient to clamp or withdraw the tested wire operate by push or pull back the insulation rod, save time and convenient. It is widely used in substations, power plants, and industrial and mining enterprises, inspection stations, electrical maintenance departments for current detection and electrical field operations. It also can replace the H/L voltage transformation ratio tester, which can measure the H/L voltage current of the primary circuit and the secondary circuit respectively, and then calculate the H/L voltage transformation ratio. The insulation rod is light, has the characteristics of moisture-proof, high temperature resistance, impact resistance, bending resistance, high insulation, scalable and so on.

Specification
Technical Specification
Function
|
Description
|
Power Supply
|
DC 6V(1.5V AAAx8)
|
Test Mode
|
Clamp CT, integration method
|
Transmission Mode
|
433Hz wireless transmission, transmission distance 30M
|
Display Mode
|
4 digital LCD display, backlight function, suitable for dim place
|
LCD Size
|
47mm×28.5mm
|
Meter Size
|
Detector: 119mm×297mm×58mm; Receiver: 78mm×165mm×42mm
|
CT Size
|
φ36mm
|
Sampling Rate
|
2 times/second
|
Measurement Range
|
0mA~1200A (50/60Hz automatic)
|
Max Resolution
|
1mA
|
Shift
|
0mA~1200A full-automatic
|
Test Accuracy
(23℃±5℃,below80%RH)
|
0mA~99.9A: ±1%±5dgt
|
100A~599A: ±1.5%±5dgt
|
600A~1200A: ±2%±5dgt
|
Data Storage
|
99 groups, in storage process "MEM" symbol display, "FULL" symbol flashes display indicate storage full
|
Line Voltage
|
Testing below 110kV, operated with insulation rod.
|
Data Hold
|
Press HOLD key to hold data in test mode, “HOLD” symbol display, press HOLD key once again cancel this function
|
Data Access
|
"MR" symbol display, can look up all storage data
|
Overflow Display
|
Exceed measure range overflow function: "OL A" symbol display
|
No Signal Indication
|
When the receiver has not received transmit signal, dynamic display “no- -”symbol
|
Auto Shut Down
|
15 minutes after boot up, the meter shuts down automatically without any operation, to reduce battery consumption
|
Battery Voltage
|
When battery voltage is lower than 4.8V, low battery voltage symbol will display and remind to replace battery.
|
Meter Weight
|
Detector: 400g, Receiver: 330g, the meter total weight: 6.38kg (include the insulation rods)
|
Working Environment
|
-10℃~50℃;below 80%rh
|
Store Environment
|
-10℃~60℃;below 70%rh
|
Interference
|
No interference of 315MHz and 433MHz same frequency signals
|
Insulation Rod Size
|
Φ32mm,1m/pcs(5pcs)
|
Insulation Withstand Voltage
|
AC110kV/rms(all 5PCS insulation rod connect, between the two ends)
|