Product Series : Wireless CT Turn Ratio Tester
It is used for current, variable ratio, angle difference testing, polarity and phase difference judgment of the first and second circuits of low-voltage current transformers.
Primary current clamp range: 0.00A~800A
Secondary current range: 0.00mA~5A
Turn ratio measurement range: 1~9999
Angle difference range: 0~360°
Storage function: store 3000 sets of data
Product Introduction
ETCR EM9600 Low Voltage CT Turn Ratio Tester, also known as transformer current variable ratio tester, transformer ratio difference tester, and current transformer variable ratio tester, is used to test the current, variable ratio, and angle difference of the first and second circuits of the medium and low-voltage current transformers in the metering device without power-off, and judge the polarity and phase difference.The tester consists of a host, a primary large-caliber current clamp, and a secondary current clamp.It provides a new type of power instrument that is safe, accurate and convenient for electricity inspectors.
1. The current clamp is made of high-performance permalloy, adopts magnetic shielding and CT digital integration technology, has strong anti-interference, high accuracy and stable testing.
2. The primary current clamp uses a large-caliber current clamp, which is suitable for various test environments, and on-site testing is convenient and fast.
3. Storage function
Technical Parameters
Power Supply | 7#alkaline dry battery (1.5V×4) |
Display Mode | 4-digit LCD display, backlight function, suitable for dim places |
LCD Size | 47mm×28.5mm |
Primary Current Clamp Test Accuracy | Range: 0.0A~800A; resolution: 0.1A; accuracy: ±0.5%FS |
Secondary Current Clamp Test Accuracy | Range: 0.00mA~5A; resolution: 0.01mA; accuracy: ±0.5%FS |
Turn Ratio Measurement Range | 1~9999 |
Turn Ratio Resolution | 0.1 |
Angle Difference Test Accuracy | Range: 0~360°; resolution: 1°; accuracy: ±3° |
Automatic Shutdown | About 15 minutes |
Battery Voltage | When the battery voltage is lower than 4.8V, the low battery voltage symbol is displayed to remind the battery to be replaced. |
Overflow Display | Over-range overflow function: ”OL A" symbol display |
Sampling Rate | 3 times/second |
Memory | 3000 groups |
Primary Current Clamp Size | Clamp jaw size: 80mm×80mm; overall size: 194mm×145mm×40mm; |
Secondary Current Clamp Size | Clamp jaw size: Φ16mm; overall size: 110mm×53mm×22mm |
Host Size | 78mm×168mm×42mm |
Weight | About 1000g |
Insulation Strength | AC3700V/rms between the clamp core and the housing |
Working Temperature & Humidity | -15℃~50℃; below 80%RH |
Storage Temperature & Humidity | -10℃~60℃; below 70%RH |
Model Comparison
Product Picture | Product Model Name | Line Voltage Level | Primarary Current Range | Secondary Current Range | Wireless Distance | Turn Ratio Range | Angle Difference Test | Others |
![]() | ETCR EM9500B Wireless High Voltage CT Turn Ratio Tester | ≤35kV | 0.0A ~800A | 0.00mA~5A | 100m | 1~9999 | -- | |
![]() | ETCR EM9500C-016 Three-Channel Wireless High Voltage CT Turn Ratio Tester | ≤35kV | 0.0A ~800A | 0.00mA~5A | 100m | 1~9999 | -- | Simultaneous measurement of 3 channels secondary currents |
![]() | ETCR EM9500C-030 Three-Channel Wireless High Voltage CT Turn Ratio Tester | ≤35kV | 0.0A ~800A | 0.00mA~10A | 100m | 1~9999 | -- | Simultaneous measurement of 3 channels secondary currents |
ETCR EM9550B Wireless High/Low Voltage CT Turn Ratio Tester | ≤35kV | 0.0A ~800A /3000A | 0.00mA~5A | 100m | 1~9999 | Yes | ||
ETCR EM9570 Multifunctional High/Low Voltage CT Turn Ratio Tester | ≤35kV | 0.0A ~800A /3000A | 0.00mA~10A | -- | 1~9999 | Yes | Harmonics/Voltage/Power measurement, Bluetooth | |
![]() | ETCR EM9600 Low Voltage CT Turn Ratio Tester | 380V/220V | 0.0A ~800A | 0.00mA~5A | -- | 1~9999 | Yes | |
![]() | ETCR EM9620 Low Voltage CT Turn Ratio Tester | 380V/220V | 0.0A~3000A | 0.00mA~5A | 100m | 1~9999 | Yes | |
![]() | ETCR EM9620B Low Voltage CT Turn Ratio Tester | 380V/220V | 0.0A~3000A | 0.00mA~5A | 100m | 1~9999 | -- |