Product Series : Wireless CT Turn Ratio Tester
Current and variable ratio testing of the first and second circuits of high and low voltage current transformers, polarity and phase difference judgment
Primary current range: 0.00A~800A
Secondary current range: 0.00mA~5A
Variable ratio measurement range: 1~9999
Wireless transmission distance: 100m
Memory: store 3000 sets of data
USB communication interface
Product Introduction
ETCR EM9500B Wireless High Voltage CT Turn Ratio Tester, also known as transformer current variable ratio tester, transformer ratio difference tester, current transformer variable ratio tester, is used for primary current, secondary current size, variable ratio, phase difference, polarity judgment of current transformers below 35kV.It is widely used in substations, power plants, power inspection departments, industrial and mining enterprises, testing stations, electrician maintenance departments for current detection, anti-theft and field electrician operations.
ETCR EM9500B Wireless High Voltage CT Turn Ratio Tester consists of a primary current clamp (high-voltage detector), a secondary current clamp, a host, a high-voltage insulating rod, monitoring software, and a communication line. The high-voltage current clamp is made of high-performance permalloy and has high test accuracy.The high-voltage current clamp has a unique automatic plug-in structure. It can easily clamp or evacuate the wire under test by pressing or withdrawing the insulating rod. The operation is safe, time-saving and fast. The insulating rod is lightweight and has the characteristics of moisture-proof, high temperature resistance, impact resistance, bending resistance, and high insulation. The insulation level is 110kV.The instrument has a storage function, a USB communication interface, and the stored data can be uploaded to a computer for historical data reading, viewing, saving, printing, etc.
1. The high-voltage current clamp is made of high-performance permalloy material, which has strong anti-interference and high test accuracy.
2. The innovative automatic plug-in and unplugging structure of the high-voltage current clamp can easily clamp or evacuate the wire under test by pressing or withdrawing the insulating rod, which is safe, time-saving and fast.
3. The high-voltage current clamp adopts wireless transmission method, with a transmission distance of 100m.
4. Storage function, storing 3000 sets of data.
5. USB communication interface.
Technical Parameters
Power Supply | DC6V alkaline dry battery LR03 (1.5V AAAX4) |
Display Mode | LCD: 128dots×64dots; backlight function, suitable for dim places |
LCD Size | Display area: 44mmX27mm |
Test Method | Clamp CT |
Primary Current Test | Range: 0.00A~800A; resolution: 0.01A; accuracy: ±0.5%FS |
Secondary Current Test | Range: 0.00mA~5A; resolution: 0.01mA; accuracy: ±0.5%FS |
Turn Ratio Measurement Range | 1~9999 |
Turn Ratio Resolution | 0.1 |
Primary Current Clamp Size | Clamp jaw size: Φ48mm;Dimensions:255mmX84mmX39mm; |
Secondary Current Clamp Size | Clamp jaw size: Φ48mm; overall size: 255mmX84mmX39mm; |
Shift Gears | Fully automatic gear shift |
Sampling Rate | 3 times/second |
Memory | 3000 groups, press the left arrow key to keep the data and store it automatically (data will not be lost if the battery is powered down or replaced) |
Data Hold | Press the left arrow key to hold the data, the HOLD symbol is displayed, and then press the HOLD key to cancel the hold |
Data Access | Press the right arrow key to enter the data access mode |
Overflow Display | Over-range overflow function: ”OL" symbol display |
No Signal Indication | Prompt “No signal” when the host does not receive the transmitted signal |
Battery Voltage | When the battery voltage is lower than 5.2V±0.3V, the low battery voltage symbol is displayed to remind the battery to be replaced. |
Primary Current Clamp Transmission Distance | Wireless transmission distance 100m |
Secondary current clamp connection line length | 2m |
Host Size | 78mm×165mm×42mm |
Weight | Receiver: about 302g (include battery); primary high voltage current clamp: about 363g (include battery) Secondary low voltage current clamp: about 156g; total weight: about 6.14kg (include accessories) |
External Interference | Avoid extra-strong electromagnetic fields; avoid 433MHz and 315MHz interference at the same frequency |
Automatic Shutdown | After about 15 minutes of power-on, the meter will automatically turn off |
Insulation Rod Size | 4300mm |
Insulation Rod Withstand Voltage | 110kV |
Insulation Strength | Host and detector: AC1000V/rms (between shell and screw) |
Working Temperature & Humidity | -15℃~50℃; below 70%RH |
Store Temperature & Humidity | -10℃~60℃; below 70%RH |
Model Comparison
Product Picture | Product Model Name | Line Voltage Level | Primarary Current Range | Secondary Current Range | Wireless Distance | Turn Ratio Range | Angle Difference Test | Others |
![]() | ETCR EM9500B Wireless High Voltage CT Turn Ratio Tester | ≤35kV | 0.0A ~800A | 0.00mA~5A | 100m | 1~9999 | -- | |
![]() | ETCR EM9500C-016 Three-Channel Wireless High Voltage CT Turn Ratio Tester | ≤35kV | 0.0A ~800A | 0.00mA~5A | 100m | 1~9999 | -- | Simultaneous measurement of 3 channels secondary currents |
![]() | ETCR EM9500C-030 Three-Channel Wireless High Voltage CT Turn Ratio Tester | ≤35kV | 0.0A ~800A | 0.00mA~10A | 100m | 1~9999 | -- | Simultaneous measurement of 3 channels secondary currents |
ETCR EM9550B Wireless High/Low Voltage CT Turn Ratio Tester | ≤35kV | 0.0A ~800A /3000A | 0.00mA~5A | 100m | 1~9999 | Yes | ||
ETCR EM9570 Multifunctional High/Low Voltage CT Turn Ratio Tester | ≤35kV | 0.0A ~800A /3000A | 0.00mA~10A | -- | 1~9999 | Yes | Harmonics/Voltage/Power measurement, Bluetooth | |
![]() | ETCR EM9600 Low Voltage CT Turn Ratio Tester | 380V/220V | 0.0A ~800A | 0.00mA~5A | -- | 1~9999 | Yes | |
![]() | ETCR EM9620 Low Voltage CT Turn Ratio Tester | 380V/220V | 0.0A~3000A | 0.00mA~5A | 100m | 1~9999 | Yes | |
![]() | ETCR EM9620B Low Voltage CT Turn Ratio Tester | 380V/220V | 0.0A~3000A | 0.00mA~5A | 100m | 1~9999 | -- |
Product Video
Friendly Links